Overview
The PE0212 series Basic PDU contains 12 AC outlets and is available in IEC or NEMA socket configurations. The PE0212 series Basic PDU features a space-saving 1U design that allows it to be mounted vertically on the outside of a rack, resulting in a more effi cient use of space in the server room, while providing 12 AC outlets.
Features
Diagram
Specifications
| Function | PE0212A | PE0212B | PE0212G |
| Electrical | |||
| Nominal Input Voltage | 100-120 VAC | 100-240 VAC | 100-240 VAC |
| Maximum Input Current | 20A Max (UL de-rated 16A Max) |
20A (Max) (UL de-rated 16A Max) |
16A (Max) |
| Input Frequency | 50-60 Hz | 50-60 Hz | 50-60 Hz |
| Input Connection | For A Plug NEMA L5-20P For A2 Plug : NEMA 5-20P |
NEMA L6-20P | IEC-320 C20 |
| Input Power | 2400VA(MAX); 1920VA(UL de-rated) |
4800VA(Max); 3840VA(UL de-rated) |
3840VA(Max) |
| Outlet Type | (12) NEMA 5-20R | (12) IEC 320 C13 | (12) IEC 320 C13 |
| Maximum Output Current (Outlet) | 20A (Max) (UL de-rated 16A Max) |
15A (Max) (UL de-rated 12A Max) |
10A (Max) |
| Maximum Output Current (Bank) | 20A (Max) (UL de-rated 16A Max) |
20A (Max) (UL de-rated 16A Max) |
16A (Max) |
| Maximum Output Current (Total) | 20A (Max) (UL de-rated 16A Max) |
20A (Max) (UL de-rated 16A Max) |
16A (Max) |
| OPD(Overcurrent Protection Device) | Yes | Yes | Yes |
| Physical Properties | |||
| Dimensions (L x W x H) | 48.80 x 4.40 x 4.50 cm (19.21 x 1.73 x 1.77 in.) |
48.80 x 4.40 x 4.50 cm (19.21 x 1.73 x 1.77 in.) |
48.80 x 4.40 x 4.50 cm (19.21 x 1.73 x 1.77 in.) |
| Weight | 0.88 kg ( 1.95 lb ) | 0.88 kg ( 1.95 lb ) | 0.88 kg ( 1.95 lb ) |
| Power Cord Length | 10ft(12#) | 10ft(12#) | 10ft(3×1.5mm2) |
| Environmental | |||
| Temperature (Operating / Storage) | 0 – 40℃ / -20 – 60℃ *When the environmental temperature comes close 40 degrees, it is recommended to lower the load to 60% to comply to the safety regulations. |
0 – 40℃ / -20 – 60℃ *When the environmental temperature comes close 40 degrees, it is recommended to lower the load to 60% to comply to the safety regulations. |
0 – 40℃ / -20 – 60℃ *When the environmental temperature comes close 40 degrees, it is recommended to lower the load to 60% to comply to the safety regulations. |
| Elevation (Operating / Storage) | 3000m | 3000m | 3000m |
| Compliance | |||
| EMC Verification | FCC Class A | FCC Class A | – |
| Safety Verification | By Request | By Request | LVD |
| Note | For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format. | ||