| Function |
PE5208A |
PE5208B |
PE5208G |
| Electrical |
| Nominal Input Voltage |
100 – 120 VAC |
100 – 240 VAC |
100 – 240 VAC |
| Maximum Input Current |
20A Max; 16A(UL de-rated) |
20A Max; 16A(UL de-rated) |
16A Max |
| Input Frequency |
50-60 Hz |
50-60 Hz |
50-60 Hz |
| Input Connection |
NEMA 5-20P |
NEMA 6-20P |
IEC 60320 C20 |
| Input Power |
2400 VA(Max); 1920 VA(UL de-rated) |
4160 VA(Max); 3328 VA(UL de-rated) |
3680 VA(Max) |
| Outlet Type |
Total : 8 x NEMA 5-20R |
Total : 7 x IEC320 C13 + 1 x IEC320 C19 |
Total : 7 x IEC320 C13 + 1 x IEC320 C19 |
| Nominal Output Voltage |
100 – 120 VAC |
100 – 240 VAC |
100 – 240 VAC |
| Maximum Output Current (Outlet) |
NEMA 5-20R: 20A(Max); 16A(UL de-rated) |
C13: 15A(Max); 12A(UL de-rated)
C19: 20A(Max); 16A(UL de-rated) |
C13: 10A(Max)
C19: 16A(Max) |
| Maximum Output Current (Bank) |
20A(Max); 16A(UL de-rated) |
20A(Max); 16A(UL de-rated) |
16A(Max) |
| Maximum Output Current (Total) |
20A(Max); 16A(UL de-rated) |
20A(Max); 16A(UL de-rated) |
16A(Max) |
| Breakers |
1 x 20A Non-Fuse Breaker |
1 x 20A Non-Fuse Breaker |
1 x 16A Non-Fuse Breaker |
| Metering |
Bank level Current, Voltage, VA , PF and KWh Monitoring |
Bank level Current, Voltage, VA , PF and KWh Monitoring |
Bank level Current, Voltage, VA , PF and KWh Monitoring |
| Outlet Switching |
None |
None |
None |
| Environment Sensor Ports |
2 |
2 |
2 |
| Metering Accuracy |
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
| Physical Properties |
| Dimensions (L x W x H) |
43.24 x 22.04 x 4.40 cm
(17.02 x 8.68 x 1.73 in.) |
43.24 x 22.04 x 4.40 cm
(17.02 x 8.68 x 1.73 in.) |
43.24 x 22.04 x 4.40 cm
(17.02 x 8.68 x 1.73 in.) |
| Weight |
2.71 kg ( 5.97 lb ) |
2.71 kg ( 5.97 lb ) |
2.71 kg ( 5.97 lb ) |
| Power Cord Length |
3 m |
3 m |
3 m |
| Environmental |
| Temperature (Operating / Storage) |
0 – 50°C / -20 – 60°C |
0 – 50°C / -20 – 60°C |
0 – 50°C / -20 – 60°C |
| Humidity (Operating & Storage) |
0 – 80% RH, Non-Condensing |
0 – 80% RH, Non-Condensing |
0 – 80% RH, Non-Condensing |
| Compliance |
| EMC Verification |
FCC, Others by Request |
FCC, Others by Request |
CE, Others by Request |
| Safety Verification |
TUV-CB, cTUVus, Others by Request |
TUV-CB, cTUVus, Others by Request |
TUV-CB, CE-LVD, Others by Request |
| Note |
For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format. |